Evaluation and solutions for induced voltage on the sheath of long underground cables in single-circuit medium voltage systems
Main Article Content
Abstract
The layout of underground cables affects the induced voltage at the sheath of the cable, which must be limited to no more than 65 V according to the electrical installation standards for Thailand to ensure safety for the operators. This paper presents the evaluation of the induced voltage at the sheath of underground cables for a single-circuit in a medium-voltage system in two formations: trefoil and flat formation with the sheath of the cable grounded at both ends. The results of the study found that the induced voltage of the trefoil formation is less and safer than the flat formation, and the practice of solving the problem of induced voltage exceeding the standard is to balance the load in each feeder to have a similar value, taking into account the shortest cable length, and install the ground wire parallel to the phase wire with a sheath voltage limiter.
Article Details
References
กองมาตรฐานระบบไฟฟ้า, การไฟฟ้าส่วนภูมิภาค. (2548). ระบบเคเบิลใต้ดิน. การไฟฟ้าส่วนภูมิภาค.
สายงานวิศวกรรม, การไฟฟ้าส่วนภูมิภาค. (2560). คู่มือการออกแบบเคเบิลใต้ดิน. การไฟฟ้าส่วนภูมิภาค.
Gouramanis, K., Kaloudas, C. G., Papadopoulos, T. A., Papagiannis, G. K., & Stasinos, K. (2011, June 19-23). Sheath voltage calculations in long medium voltage power cables [Paper presentation]. 2011 IEEE Trondheim PowerTech, Trondheim, Norway. https://doi.org/10.1109/ptc.2011.6019234
Guevara, J. E., Colqui, J. S., Bautista, J. P., & Pissolato Filho, J. (2023). Analysis of induced voltages on the sheath of single-circuit underground power lines-Part I: Without phases transposition. In 2023 IEEE Colombian Caribbean Conference (C3) (pp. 1–6). IEEE. https://doi.org/10.1109/C359124.2023.10324831
Guevara, J. E., Colqui, J. S. L., Bautista, J. P., & Filho, J. P. (2023, October 17-20). Analysis of induced voltages on the sheath of double-circuit underground power lines - Part I: Without phases transposition [Paper presentation]. 2023 IEEE XXX International Conference on Electronics, Electrical Engineering and Computing (INTERCON), Lima, Peru. https://doi.org/10.1109/intercon59652.2023.10326027
Guevara, J. E., Ruiz, W. G. F., Colqui, J. S. L., & Pissolato Filho, J. (2024). Evaluation of mixed systems for sheath bonding of single-circuit underground power lines. In SoutheastCon 2024 (pp. 486–491). IEEE.
Guevara Asorza, J. E., Colqui, J. S. L., Kurokawa, S., & Pissolato Filho, J. (2024). Analysis of increased induced voltages on the sheath of double-circuit underground transmission lines guaranteeing ampacity. Energies, 17(7), 1637. https://doi.org/10.3390/en17071637
International Electrotechnical Commission. (2011). Low-voltage electrical installations – Part 5-54: Selection and erection of electrical equipment – Earthing arrangements and protective conductors (IEC 60364-5-54:2011).
Lee, J.-B., & Jung, C.-K. (2012). Technical review on parallel ground continuity conductor of underground cable systems. Journal of International Council on Electrical Engineering, 2(3), 250–256. https://doi.org/10.5370/jicee.2012.2.3.250
Maneepeth, P., Thararak, P., Jirapong, P., & Karaaom, C. (2021, May 12-14). Mitigation of induced currents and overvoltages in metallic sheath of 115 kV underground cable using sheath voltage limiter and parallel ground continuity conductor [Paper presentation]. 2021 18th International Conference on Electrical Engineering/Electronics, Computer, Telecommunications and Information Technology (ECTI-CON), Chiang Mai, Thailand. https://doi.org/10.1109/ieecon51072.2021.9440357
Papadopoulos, T. A., Charalambous, C. A., & Chrysochos, A. I. (2024). Important insights into steady-state calculations of voltages and currents in complex sheath bonding configurations of single-core cables. Electric Power Systems Research, 235, 110859. https://doi.org/10.1016/j.epsr.2024.110859
Shaban, M., Salam, Md. A., Ang, S. P., & Voon, W. (2014, March 31-April 3). Calculation of sheath voltage of underground cables using various configurations [Paper presentation]. 10th IET International Conference on Developments in Power System Protection (DPSP 2014), Copenhagen, Denmark. https://doi.org/10.1049/cp.2014.1074
Shaban, M., Salam, Md. A., Ang, S. P., Norfauzi, Md., Wen, F., & Voon, W. (2015, November 1-4). Calculation of induced sheath voltage for transposed and untransposed cable conductors [Paper presentation]. TENCON 2015 - 2015 IEEE Region 10 Conference, Macao, China. https://doi.org/10.1109/tencon.2015.7372833
Shaban, M., Salam, Md. A., Ang, S. P., Poulose, M. M., & Voon, W. (2015, November 1-4). Induced sheath voltage in double circuit [Paper presentation]. TENCON 2015 - 2015 IEEE Region 10 Conference, Macao, China. https://doi.org/10.1109/tencon.2015.7373111